Kees DFG (DIRECT FIRED GAS) MAKE-UP AIR UNITS Manual do Utilizador

Consulte online ou descarregue Manual do Utilizador para Exaustores Kees DFG (DIRECT FIRED GAS) MAKE-UP AIR UNITS. Kees DFG (DIRECT FIRED GAS) MAKE-UP AIR UNITS User Manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 16
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 0
KEES, INC.
Installation & Maintenance Manual
DFG Series Direct Gas Fired
Make-up Air Heaters
Table of Contents
Page # Topic
1 Description of Operation
1 Receiving the Unit
1 Positioning the Unit
1 Curbing the Unit
2 Piping the Unit
2 Wiring the Unit
3 Optional Equipment
5 Controls Description
9 Troubleshooting Guide
13 Start-up of the Unit
15 Maintenance Schedule
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. Don't touch electrical switches.
3. Extinguish any open flame.
4. Immediately call your gas supplier.
FOR YOUR SAFETY
The use and storage of gasoline or other
flammable vapors and liquids in open
containers in the vicinity of this appliance is
hazardous.
WARNING: Improper installation, adjustment,
alteration, service or maintenance can cause
property damage, injury or death. Read the
installation, operating and maintenance
instructions thoroughly before installing or
servicing this equipment.
Vista de página 0
1 2 3 4 5 6 ... 15 16

Resumo do Conteúdo

Página 1 - KEES, INC

KEES, INC.Installation & Maintenance ManualDFG Series Direct Gas FiredMake-up Air HeatersTable of ContentsPage # Topic 1 Description of Operatio

Página 2 - INSTALLATION INSTRUCTIONS

9TROUBLE SHOOTING GUIDEIf a service problem should occur, the following guide can be used to isolate and correctthe problem.IMPORTANT:Before this heat

Página 3

10B. BLOWER MOTOR STARTER GOES OUT ON OVERLOAD. REMEDYProbable1. Motor drawing too many amps. Slow blower RPM down.Cause: 2. Loose wiring. Check wire

Página 4 - OPTIONAL EQUIPMENT

11D. PILOT LIGHTS, BUT FLAME SAFETYLOCKS OUT AFTER 30 SECONDS REMEDYProbable1. Defective flame rod. Check porcelain for cracks.Cause:Replace rod if cr

Página 5

12G. UNIT UNDER-FIRED (TemperatureRise Too Low) REMEDYProbable1. Lack of gas pressure. Adjust gas pressure as stated on Cause:unit identification plat

Página 6

13START-UP OF THE UNIT1. Turn the remote switch to the "OFF" position.2. Turn the main disconnect switch to the "OFF" position.3.

Página 7

1420. Open the main gas shutoff valve. Disconnect the wire from the "A4" terminal block. Thiswill cause the unit to call for continuous hi

Página 8

15MAINTENANCE SCHEDULEService and maintenance should be performed four times a year (three-month intervals)or after every 2,000 hours of operation. T

Página 9

1INSTALLATION INSTRUCTIONSDescription of OperationThe KEES DFG series heater is a direct gas fired heater using 100% outside air. It isdesigned for o

Página 10 - TROUBLE SHOOTING GUIDE

2Piping the UnitApplicable codes and standards must be followed in sizing and installing the gas piping. A manual gas shutoff valve is provided for fi

Página 11

3OPTIONAL EQUIPMENTLOW TEMPERATURE LIMIT SWITCHThis control is commonly called a Freeze Stat. This unit mounted, low limit thermostat will shut thebl

Página 12

4CONTROL SYSTEM DIAGNOSTIC INDICATORThis component is used as a diagnostic tool for troubleshooting burner problems. It attaches to theburner control

Página 13

5HIGH PRESSURE REGULATORIt is necessary to install a high-pressure regulator upstream of the unit if the incoming gas pressure isgreater than ½ PSIG.

Página 14 - START-UP OF THE UNIT

62. DAMPER MOTORThe function of the damper motor is to power open or spring return close the dampers on thedischarge or intake of the unit. It will s

Página 15

77. LOW GAS PRESSURE SWITCHThe function of this switch is to de-energize the burner circuit if the gas pressure to the burner isbelow its setting. Ma

Página 16 - MAINTENANCE SCHEDULE

813. REMOTE TEMPERATURE SELECTORThe function of this dial is to set the desired discharge temperature the unit is to supply. This dialworking in con

Comentários a estes Manuais